CONTROL AND POWER SUPPLY FLEXIBLE CABLES | Technical Data Sheet |
|
|
APPLICATIONS
TECHNOFLEKS LiY11Y-Nr 300/500 V and TECHNOFLEKS LiY11Yżo-Nr 300/500 V are flexible cables designed for wet or dry locations and intended for control, protection and monitoring systems or power supply, all in power engineering. The cables are also intended for wiring industrial plants, such as production lines, air-conditioning equipment etc.
Polyurethane sheath offers enhanced protection against mechanical damage, particularly to abrasion and tear, also resistant to oils, petrol, bacteria and ultraviolet radiation.
The cables are designed to offer high flexibility combined with tensile strength.
Cables are dedicated to work in heavy duty conditions.
The cables are suitable for indoor and outdoor installations connecting fixed and movable equipment.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,
- black PVC insulation and white conductor numbers printed on it for identification, additional green-yellow protective conductor in TECHNOFLEKS LiY11Yżo-Nr 300/500 V cable,
- insulated conductors laid-up in layers, green-yellow protective conductor located in the outer layer in TECHNOFLEKS LiY11Yżo-Nr 300/500 V cable,
- polyurethane cable sheath, grey RAL 7001, other colours also available.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.5 |
0.75 |
1.0 |
1.5 |
2.5 |
4.0 |
DC conductor resistance at 20°C, maximum |
Ω/km |
39.0 |
26.0 |
19.5 |
13.3 |
7.98 |
4.95 |
Conductor cross-section |
mm2 |
6.0 |
10 |
16 |
25 |
35 |
50 |
DC conductor resistance at 20°C, maximum |
Ω/km |
3.30 |
1.91 |
1.21 |
0.780 |
0.554 |
0.386 |
Operating voltage Uo/U Voltage test Insulation resistance, minimum Conductor temperature limit in work conditions at short-circuit |
300/500 V 3.0 kV rms 20 MΩ·km
+ 70°C + 150°C |
Operating temperature range for fixed installation for movable installation Minimum bending radius Cable combustibility Combustibility tests
|
from - 40 to + 80°C from - 15 to + 70°C 7.5 x cable diameter flame retardant PN-EN 60332-1-2, IEC 60332-1-2
|
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.