PVC INSULATED AND SHEATHED CONTROL CABLES Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

YKSYżo 0,6/1 kV and YKSY 0,6/1 kV control cables are designed for control, protection and monitoring systems in power engineering, also for electric power distribution.

The cables are suitable for industrial applications, such as production plants or air-conditioning systems operating in dry and wet locations, also for outdoor installations, in cable ducts or for direct earth burial.

CONSTRUCTION                                                                                                           

- bare annealed copper conductors meeting requirements of class 1 per PN-EN 60228 standard,

- PVC insulation, colour code insulation in each layer:

              brown conductor as a counter, blue directional conductor and other conductors of any colour

              with the exception of green, yellow, brown and blue,

              YKSYżo 0,6/1 kV green-yellow protective conductor is positioned as a counter conductor in the           outer layer instead of conductor of brown,

- insulated conductors laid-up in a cable core,

- cable core wrapped in polyester tape,

- black PVC cable sheath, other colours also available.

AVAILABLE UPON REQUEST

YKSYżo-O 0,6/1 kV and YKSY-O 0,6/1 kV - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN-EN 60811-404.

YnKSYżo 0,6/1 kV and YnKSY 0,6/1 kV - cables of reduced combustibility, sheathed with special self-extinguishing PVC of high oxygen index and pass combustibility test according to PN-EN 60332-3 standard.

YKSwYżo 0,6/1 kV and YKSwY 0,6/1 kV - cables with inner covering extruded directly on a cable core, recommended for direct earth burial.

XnKSXSżo 0,6/1 kV and XnKSXS 0,6/1 kV - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.

Steel wire or steel tape armoured cables as above applied in locations where enhanced protection against mechanical damages is required.

 

CHARACTERISTICS

Conductor cross-section

mm2

1

1,5

2,5

4

6

10

16

DC conductor resistance at 20°C, maximum

Ω/km

18.1

12.1

7.41

4.61

3.08

1.83

1.15

Operating voltage Uo/U    0.6/1 kV
Voltage test    4 kV rms
Insulation resistance, minimum    20 MΩ·km

Conductor temperature limit
      in work conditions          +70°C
      in short-circuit               +160°C

Temperature range
      during operation            from - 30 to + 70°C
      during installation          from   - 5 to + 50°C

Minimum bending radius      12 x cable diameter

Cable combustibility             flame retardant

Combustibility tests              PN-EN 60332-1-2, IEC 60332-1-2

Reference standards            IEC 60502-1, PN-93/E-90403, PN-HD 603 S1

 

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.