YKSYFtynżo 0,6/1 kV and YKSYFtyn 0,6/1 kV armoured control cables are designed for control, protection and monitoring systems in power engineering, also for electric power distribution.

The cables are suitable for industrial applications, such as production plants or air-conditioning systems operating in dry and wet locations, also for outdoor installations, in cable ducts or for direct earth burial.

Steel tape armour offers enhanced protection against mechanical damages and rodent attack, it has also shielding properties.

The cable sheath is then made of special self-extinguishing PVC of reduced combustibility and pass combustibility test according to EN 60332-3 standard.

CONSTRUCTION                                                                                                           

- bare annealed copper conductors meeting requirements of class 1 per PN-EN 60228 standard,

- PVC insulation, colour code insulation in each layer:

              brown conductor as a counter, blue directional conductor and other conductors of any colour

              with the exception of green, yellow, brown and blue,

              YKSYFtynżo 0,6/1 kV green-yellow protective conductor is positioned as a counter conductor in the outer layer instead of conductor of brown,

- insulated conductors laid-up in a cable core,

- PVC cable sheath,

- galvanized steel tape armour,

- black PVC cable covering, other colours also available.

AVAILABLE UPON REQUEST

YKSYFtyżo-O 0,6/1 kV and YKSYFty-O 0,6/1 kV - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN‑EN 60811-404.

XnKSXSFtxnżo 0,6/1 kV and XnKSXSFtxn 0,6/1 kV - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.

CHARACTERISTICS

Conductor cross-section

mm2

1

1,5

2,5

4

6

10

16

DC conductor resistance at 20°C, maximum

Ω/km

18.1

12.1

7.41

4.61

3.08

1.83

1.15

Operating voltage Uo/U    0.6/1 kV
Voltage test    4 kV rms
Insulation resistance, minimum    20 MΩ·km

Conductor temperature limit
      in work conditions          +70°C
      in short-circuit               +160°C

Temperature range
      during operation            from - 30 to + 70°C
      during installation          from   - 5 to + 50°C

Minimum bending radius      12 x cable diameter

Cable combustibility             flame retardant

Combustibility tests               PN-EN 60332-1-2, IEC 60332-1-2

                   ³ 25 mm2         PN-EN 60332-3-23, IEC 60332-3-23 (cat. B)

                   < 25 mm2        PN-EN 60332-3-24, IEC 60332-3-24 (cat. C)

Reference standards             IEC 60502-1, PN-93/E-90403, PN-HD 603 S1

The cable meets requirements of the low voltage directive 2014/35/EU