INSTRUMENTATION CABLES | Technical Data sheet |
|
|
APPLICATIONS
EGSF and EGFA instrumentation cables are intended for control and instrumentation circuits, for signal, monitoring and data processing systems and for analogue or digital data transmission, all in industrial electronics applications, allowing particularly for conditions met in chemical, petrochemical and paper industries.
The cables are protected by an overall electrostatic shield against external electric interferences.
Steel tape armour in EGFA cables offers enhanced protection against mechanical damages and rodent attack.
The cables can also be used for power supply to small auxiliary devices on condition that current-carrying capacity limit (see our Technical Guide) is not exceeded.
The cables are suitable for fixed indoor and outdoor installations.
Sheathing PVC of high oxygen index is UV radiation and weather resistant, is self-extinguishing and flame retardant. The cables pass combustibility test according to PN-EN 60332-3 standard.
The cables are oil-resistant and offer enhanced resistance to aliphatic hydrocarbons.
CONSTRUCTION
- bare annealed copper wire conductors,
05 – 0.50 mm2 (1x0.8 mm),
09 – 0.88 mm2 (7x0.4 mm)
15 – 1.50 mm2 (7x0.52 mm),
- heat resistant PVC insulation,
- insulated conductors twisted into:
pairs IP - colour code: white and red insulation and pair number printed on it,
triads IT - colour code: white, red and blue insulation and triad number printed on it,
quads IQ - colour code: white, red, blue and yellow insulation for identification,
- pairs, triads or quads laid-up in layers,
- cable core wrapped in polyester tape,
- overall electrostatic shield incorporating aluminium-polyester tape and stranded annealed tinned copper drain wire, cross-section 0.22 mm2 (7x0.2 mm),
- special PVC cable sheath, blue (RAL 5012), other colours also available,
- steel tape armour for EGFA cable,
- special PVC cable covering, blue (RAL 5012), other colours also available.
CHARACTERISTICS
DC loop resistance at 20°C, maximum:
0.50 mm2 conductor 75.0 Ω/km
0.88 mm2 conductor 42.8 Ω/km
1.50 mm2 conductor 24.2 Ω/km
Resistance unbalance, maximum:
0.50 mm2 conductor 1.120 Ω/km
0.88 mm2 conductor 1.070 Ω/km
1.50 mm2 conductor 0.605 Ω/km
conductor/conductor 1500 V rms
conductor/screen 1000 V rms
Operating voltage Uo/U 300/300 V
Voltage test
conductor/conductor 1500 V rms
conductor/screen 1000 V rms
Insulation resistance, minimum 500 MΩ·km
Mutual capacitance, max (this value may be 30% higher for one pair or triad):
0.50 mm2 conductor 145 nF/km
0.88 mm2 conductor 160 nF/km
1.50 mm2 conductor 150 nF/km
Operating temperature range
during operation from - 30 to + 90°C
during installation from - 5 to + 70°C
Minimum bending radius 15 x cable diameter
Resistance to aliphatic hydrocarbons NF M 87-202 Annex A
Oil resistance PN-EN 60811-404
Cable combustibility flame retardant
Combustibility tests PN-EN 60332-1-2, IEC 60332-1-2
Reference standards NF M 87-202
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and pair, triad or quad counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.