FLEXIBLE HOOK-UP WIRES | Technical Data sheet |
|
|
APPLICATIONS
TLY are telecommunication hook-up wires intended for use in remote control, signal and data transmission and industrial data processing systems and computer networks.
Generally, they are designed for control cabinets, electronic devices and others as interconnection cables for electronic modules, equipment and instruments.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request),
- PVC insulation - identification colour code in accordance with PN-91/T-90206,
- in case of multiwire cables, insulated conductors twisted into pairs, triads or quads.
AVAILABLE UPON REQUEST
TLYc - wires with heat resistant PVC insulation up to 90°C (on request for temperatue up to 105°C – TLYc 105°C).
TLYd - wires with reinforced (thickened) insulation.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.055 |
0.079 |
0.124 |
0.22 |
0.35 |
0.50 |
DC conductor resistance at 20°C, maximum single-wires multi-wires |
Ω/km |
365.0 380.0 |
242.0 252.0 |
155.0 161.0 |
89.3 92.0 |
57.2 60.0 |
38.8 40.0 |
Insulation resistance, minimum |
MΩ·km |
50 |
50 |
50 |
200 |
200 |
200 |
Voltage test |
V rms |
500 |
500 |
500 |
1000 |
1000 |
1000 |
Operating voltage Operating temperature range for fixed installation for movable installation
|
150 V
from - 20 to + 70°C from - 5 to + 50°C
|
Minimum bending radius Wire combustibility Combustibility tests
Reference standards |
7.5 x wire diameter flame retardant PN-EN 60332-1-2, IEC 60332-1-2 PN-EN 60332-2-2, IEC 60332-2-2 PN-91/T-90200, PN-91/T-90206 |
The cable meets requirements of the low voltage directive 2014/35/EU
c - tinned copper conductor.
Other conductor diameters and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.