FIRE RESISTANT HALOGEN FREE POWER CABLES | Technical Data sheet |
|
|
APPLICATIONS
NHXCH FE180 PH30/E30 0,6/1 kV fire resistant and halogen free power cables, are intended for power supply to fire protection equipment in objects of sharp fire protection requirements, particularly in fire alarm and fire automatic control systems.
The cables shall be applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required.
Functions of the cables are maintained – power is supplied to equipment which must operate in fire conditions and during fire fighting (e.g. water pumps in fire extinguishing systems, smoke removing fans, emergency lighting and elevators).
The cables are certified by Scientific and Research Centre for Fire Protection - National Research Institute (Centrum Naukowo-Badawcze Ochrony Przeciwpożarowej - PIB) at Józefów.
The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive.
The cables are resistant to water in accordance with EN 50200 Annex E and can be used in fire protected rooms with fixed pressure water spraying fire extinguishing systems (sprinkler zones).
The cables are suitable for fixed indoor and outdoor installations. UV radiation protection is required for outdoor installations. Laying cables in water or direct earth burial are only permitted if additional protection is used.
CONSTRUCTION
- bare annealed copper conductors meeting requirements of PN-EN 60228 standard:
RE - class 1 single wire round conductor,
RM - class 2 multiwire round conductor,
- mica tape and halogen free cross-linked compound insulation – colours:
up to 5 wires in accordance with PN-HD 308,
above 5 wires black and white conductor number printed on it,
- insulated conductors laid-up into a cable core,
- inner covering made of halogen free compound,
- concentric conductor formed by bare copper wires with counter helix of copper tape over the inner sheath,
- concentric conductor wrapped in polyester tape,
- orange cable sheath made of halogen free compound type HM4 according to HD 604 S1 and VDE 0276-604, (oxygen index bigger than 35%).
CHARACTERISTICS
Operating voltage 0.6/1 kV
Voltage test 4.0 kV rms
Insulation resistance at 90°C, minimum 1011 Ω·cm
Inductance, approximate 0.7 mH/km
Conductor temperature limit
in work conditions +90°C
in short-circuit +250°C
Corrosivity of emitted gases per PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2
pH, approximate 6.8
conductivity, approximate 0.4 µS/mm
Smoke density per PN-EN 61034-2, IEC 61034-2
light transmittance, minimum 70%
Operating temperature range
during operation from -30 to +90°C
during installation from -5 to +50°C
Minimum bending radius: 15 x cable diameter
Cable combustibility fire resistant
Combustibility tests PN-EN 60332-1-2, IEC 60332-1-2, PN-EN 60332-3-24, IEC 60332-3-24 (cat. C)
Circuit integrity *
E30 DIN 4102-12
PH30 PN-EN 50200 Annex E or PN-EN 50362
Insulation integrity FE180 IEC 60331-21, IEC 60331-11
Reference standards AT-0603-0496/2016, WT-TK-44, DIN VDE 0266, PN-HD 604 S1
*Circuit integrity is dependent on installation method.
Cable installation - Only certified cable fixing systems shall be used. Systems certified according to DIN 4102 part 12 are recommended.
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.