FIRE ALARM CABLES | Technical Data sheet |
|
|
APPLICATIONS
YnTKSY, YnTKSYekw and YnTKSXekw cables are intended for fire alarm and fire automatic control systems also for data processing systems and for analogue or digital data transmission, all in industrial electronics applications.
The cables are certified by Scientific and Research Centre for Fire Protection - National Research Institute (Centrum Naukowo-Badawcze Ochrony Przeciwpożarowej - PIB) at Józefów.
The cables are protected by an overall electrostatic shield against external electric interferences.
The cables are suitable for fixed indoor installations.
CONSTRUCTION - YnTKSY and YnTKSYekw
- bare annealed copper single wire round conductors of diameter 0.8 mm, 1.0 mm, 1.4 mm and 1.5 mm,
- PVC insulation - colours in accordance with PN-92/T-90321 standard,
- insulated conductors twisted into pairs or a quad,
- pairs laid-up into a cable core,
- cable core wrapped in a polyester tape,
- overall electrostatic shield incorporating a plastic laminated metal foil and a tinned copper drain wire in YnTKSYekw cable,
- special (oxygen index bigger than 29%) PVC cable sheath, red RAL 3000.
CONSTRUCTION - YnTKSXekw
- bare annealed copper single wire round conductors of diameter 1.05 mm,
- polyethylene (PE) insulation - colours in accordance with PN-92/T-90321 standard,
- żyły izolowane skręcone w pary lub w czwórkę,
- insulated conductors twisted into pairs or a quad,
- cable core wrapped in a polyester tape,
- overall electrostatic shield incorporating a plastic laminated metal foil and a tinned copper drain wire,
- special (oxygen index bigger than 29%) PVC cable sheath, red RAL 3000.
CHARACTERISTICS
Cable type |
|
YnTKSY |
YnTKSYekw |
YnTKSXekw |
||||||
Conductor diameter |
mm |
0.8 |
1.0 |
1.4 |
1.5 |
0.8 |
1.0 |
1.4 |
1.5 |
1.05 |
DC loop resistance at 20oC, maximum |
Ω/km |
75 |
48 |
24 |
24 |
75 |
48 |
24 |
24 |
48 |
Capacitance between conductors at 1 kHz - maximum |
nF/km |
120 |
120 |
120 |
120 |
200 |
200 |
200 |
200 |
65 |
- average |
100 |
100 |
100 |
100 |
140 |
140 |
140 |
140 |
63 |
Operating voltage 150 V
Voltage test 1500 V rms
Insulation resistance, minimum 20 MΩ∙km
Inductance, approximate 0,7 mH/km
Operating temperature range
during operation from - 30 to + 80°C
during installation from - 5 to + 70°C
Minimum bending radius 10 x cable diameter
Cable combustibility flame retardant
Combustibility tests PN-EN 60332-1-2
Reference standards AT-0603-0048/2011/2016, WT-TK-4, PN - 92/T-90320, PN - 92/T-90321
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.