TELECOMMUNICATION CABLES | Technical Data sheet |
|
|
APPLICATIONS
YnTKSXekp 1x2x0,4c mm and Yn-YTKSXekp nx(1x2x0,4c) mm are multipair, pair inividually shielded cables intended for control and instrumentation circuits, for signal, monitoring and data processing systems and for analogue or digital data transmission, all in industrial electronics applications.
Cables provide data transmission in the following systems: ISDN, PCM and others.
Shielded pair structure substantially decreases mutual influence between signals transmitted along the cable.
The cables are suitable for indoor installations.
CONSTRUCTION YnTKSXekp
- tin-plated copper single wire round conductors of diameter 0.4 mm,
- PVC insulation - identification colour code: black, grey,
- insulated conductors twisted into pair,
- pair shield incorporating aluminium-polyester tape and stranded annealed tinned copper drain wire,
- special (oxygen index bigger than 29%) PVC cable sheath, grey RAL 7035, other colours also available.
CONSTRUCTION Yn-YTKSXekp
- tin-plated copper single wire round conductors of diameter 0.4 mm,
- PVC insulation - identification colour code: black, grey,
- insulated conductors twisted into pairs,
- pair shield incorporating aluminium-polyester tape and annealed tinned copper single drain wire,
- shielded pairs sheathed with PVC to insulate one shield from another, grey RAL 7035 and printed black number of pair,
- shielded and sheathed pairs laid-up in layers,
- special self-extinguishing (oxygen index bigger than 29%) PVC cable sheath, grey RAL 7035, other colours also available.
CHARACTERISTICS
Characteristic impedance Effective capacitance at 1 kHz Attenuation loss, max - at frequency 1MHz Insulation resistance, min Operating voltage Voltage test |
120 ± 15 Ω 50 ± 5 nF/km 6 dB/100 m 1000 MΩ·km 150 V 1500 V rms |
DC loop resistance at 20°C, max Operating temperature range during operation during installation Minimum bending radius Cable combustibility Combustibility tests
Reference standards |
290 Ω/km
from - 30 to + 70 °C from - 10 to + 50 °C 15 x cable diameter flame retardant PN-EN 60332-1-2, IEC 60332-1-2 PN-EN 60332-3-24, IEC 60332-3-24 (cat. C) PN-92/T-90320 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other diameters and pair counts available on request.