PVC INSULATED AND SHEATHED, STEEL WIRE ARMOURED AND PVC OVERSHEATHED POWER CABLES | Technical Data sheet |
|
|
APPLICATIONS
YKYFoynżo 0,6/1 kV and YKYFoyn 0,6/1 kV armoured power cables are designed for electric power transmission. They are also applied in power circuits in industrial plants and power stations and in local distribution networks.
The cables are suitable for indoor and outdoor installations, for laying in cable ducts and for direct earth burial.
Galvanized steel wire armour provides carrying an axial load of the cable during installation and exploitation. It also offers enhanced protection against mechanical damages and rodent attack, as well as shielding properties.
The cable covering is then made of special self-extinguishing PVC of reduced combustibility and pass combustibility test according to EN 60332-3 standard.
CONSTRUCTION
- bare annealed copper conductors meeting requirements of PN-EN 60228 standard:
RE - class 1 circular single-wire,
RM - class 2 circular multi-wire,
SM - class 2 sector shaped multi-wire,
- PVC insulation - colours in accordance with PN-HD 308 standard, green-yellow protective conductor in YKYFoynżo 0,6/1 kV cable,
- insulated conductors laid-up in a cable core,
- PVC cable sheath,
- galvanized steel wire armour,
- black PVC cable covering, other colours also available.
AVAILABLE UPON REQUEST
YKYFoyżo-O 0,6/1 kV and YKYFoy-O 0,6/1 kV - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN-EN 60811-404.
XnKXSFoxnżo 0,6/1 kV and XnKXSFoxn 0,6/1 kV - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.
CHARACTERISTICS
Operating voltage Uo/U 0.6/1 kV
Voltage test 4 kV rms
Insulation resistance, minimum 20 MΩ·km
Conductor temperature limit
in work conditions +70°C
in short-circuit +160°C
Temperature range
during operation from - 30 to + 70°C
during installation from - 5 to + 50°C
Minimum bending radius
single wire cables 15 x cable diameter
multi wire cables 12 x cable diameter
Cable combustibility flame retardant
Combustibility tests PN-EN 60332-1-2, IEC 60332-1-2
³ 25 mm2 PN-EN 60332-3-23, IEC 60332-3-23 (cat. B)
< 25 mm2 PN-EN 60332-3-24, IEC 60332-3-24 (cat. C)
Reference standards IEC 60502-1, PN-93/E-90401, PN-HD 603 S1
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.