HEAT RESISTANT SILICONE CABLES | Technical Data sheet |
|
|
APPLICATIONS
SiHF are flexible silicone insulated and sheathed cables intended for use in wide range of temperature. The cables are suitable for industrial applications, such as steel plants or cement, glass and ceramic factories. They are also used in lighting devices and systems.
The cables are halogen free, as well oil and chemical resistant.
CONSTRUCTION
- flexible, multiwire conductors, stranded of tin-plated annealed copper wires, meeting requirements of class 5 per PN-EN 60228,
- silicone rubber insulation,
- colour of insulation:
2 wires: brown, blue,
up to 5 wires: colours in accordance with PN-HD 308 standard,
above 5 wires: black and white conductor number printed on it,
from 3 wires: with a green-yellow protective conductor,
- insulated conductors laid-up in layers,
- silicone rubber cable sheath, red-brown colour.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0,5 |
0,75 |
1,0 |
1,5 |
2,5 |
4,0 |
6,0 |
10,0 |
16,0 |
DC conductor resistance at 20°C, maximum |
Ω/km |
40.1 |
26.7 |
20.0 |
13.7 |
8.21 |
5.09 |
3.39 |
1.95 |
1.24 |
Operating voltage Uo/U 300/500 V
Voltage test 2000 V rms
Insulation resistance, minimum 20 MΩ·km
Operating temperature range(adequate ventilation provided) from - 60 to + 180°C
temporary + 200°C
Minimum bending radius
for movable installation 7.5 x cable diameter
for fixed installation 4 x cable diameter
Halogen-free PN-EN 60754-1, PN-EN 60754-2
Cable combustibility flame retardant
Combustibility tests PN-EN 60332-1-2, IEC 60332-1-2
The cable meets requirements of the low voltage directive 2014/35/EU
G - cables with green-yellow protective conductor
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.