CABLES FOR ALARM AND SECURITY SYSTEMS | Technical Data sheet |
|
|
APPLICATIONS
SCYwYw are heat resistant cables intended for connection of sensors, detectors, receptors and other signalling devices, in control loops of internal alarm systems.
The cables are suitable for indoor installations connecting fixed and movable equipment.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires, cross-section 0.22mm2 (7x0.2 mm),
- heat resistant PVC insulation - identification colour code: red, blue, yellow, black, white, green, orange, brown, grey, pink,
- insulated conductors laid-up into a cable core,
- heat resistant PVC cable sheath, white RAL 9010, other colours also available.
CHARACTERISTICS
Conductor cross-section 0,22 mm2
DC conductor resistance at 20°C, maximum 85 Ω/km
Operating voltage 150 V
Voltage test 700 V rms
Insulation resistance, minimum 50 MΩ·km
Operating temperature range
for fixed installation from - 40 to + 90°C
for movable installation from - 25 to + 90°C
Minimum bending radius 7.5 x cable diameter
Cable combustibility flame retardant
Combustibility tests PN-EN 60332-1-2, IEC 60332-1-2
Reference standards BS 4737 section 3.30
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.