CABLES FOR ALARM AND SECURITY SYSTEMS Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

SCYwYw are heat resistant cables intended for connection of sensors, detectors, receptors and other signalling devices, in control loops of internal alarm systems.

The cables are suitable for indoor installations connecting fixed and movable equipment.

CONSTRUCTION

- flexible, multiwire conductors, stranded of bare annealed copper wires, cross-section 0.22mm2 (7x0.2 mm),

- heat resistant PVC insulation - identification colour code: red, blue, yellow, black, white, green, orange, brown, grey, pink,

- insulated conductors laid-up into a cable core,

- heat resistant PVC cable sheath, white RAL 9010, other colours also available.

CHARACTERISTICS

Conductor cross-section    0,22 mm2

DC conductor resistance at 20°C, maximum    85 Ω/km

Operating voltage    150 V

Voltage test    700 V rms

Insulation resistance, minimum    50 MΩ·km

Operating temperature range
      for fixed installation               from   - 40 to + 90°C
      for movable installation          from   - 25 to + 90°C

Minimum bending radius              7.5 x cable diameter

Cable combustibility                     flame retardant

Combustibility tests                      PN-EN 60332-1-2, IEC 60332-1-2

Reference standards                    BS 4737 section 3.30

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.