XLPE INSULATED AND HALOGEN FREE SHEATHED CONTROL CABLES | Technical Data sheet |
|
|
APPLICATIONS
XnKSXSżo-Nr 0,6/1 kV and XnKSXS-Nr 0,6/1 kV control cables are designed for control, protection and monitoring systems in power engineering, also for electric power distribution.
The cables are suitable for industrial applications, such as production plants or air-conditioning systems operating in dry and wet locations, also for outdoor installations, in cable ducts or for direct earth burial.
Halogen free cables shall be applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required. The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive.
CONSTRUCTION
- bare annealed copper conductors meeting requirements of class 1 per PN-EN 60228 standard,
- black cross-linked polyethylene (XLPE) insulation and white conductor number printed on it; a green-yellow protective conductor in the outer layer in XnKSXSżo-Nr 0,6/1 kV cable,
- insulated conductors laid-up in layers,
- cable core wrapped in polyester tape,
- cable sheath made of halogen free compound (HFFR), black, other colours also available.
AVAILABLE UPON REQUEST
XnKSwXSżo-Nr 0,6/1 kV and XnKSwXS-Nr 0,6/1 kV - cables with inner covering extruded directly on a cable core, recommended for direct earth burial.
Steel wire or steel tape armoured cables as above applied in locations where enhanced protection against mechanical damages is required.
CHARACTERISTICS
Conductor cross-section |
mm2 |
1 |
1,5 |
2,5 |
4 |
6 |
10 |
16 |
DC conductor resistance at 20°C, maximum |
Ω/km |
18.1 |
12.1 |
7.41 |
4.61 |
3.08 |
1.83 |
1.15 |
Operating voltage Uo/U |
0.6/1 kV |
Voltage test |
4 kV rms |
Insulation resistance, minimum |
100 MΩ·km |
Corrosivity of emitted gases per |
PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2 |
pH appr. |
6,8 |
conductivity appr. |
0,4 µS/mm |
Smoke density per |
PN-EN 61034-2, IEC 61034-2 |
minimum light transmittance |
70% |
Conductor temperature limit |
|
in work conditions |
+90°C |
in short-circuit |
+250°C |
Temperature range |
|
during operation |
from -30 to +70°C |
during installation |
from -5 to +50°C |
Minimum bending radius |
12 x cable diameter |
Cable combustibility |
flame retardant |
Combustibility tests |
PN-EN 60332-1-2, IEC 60332-1-2 PN-EN 60332-3-24, IEC 60332-3-24 |
Reference standards |
IEC 60502-1, PN-HD 604 S1, DIN VDE 0266 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.