CONTROL CABLES FOR INDUSTRIAL ELECTRONIC APPLICATIONS | Technical Data sheet |
|
|
APPLICATIONS
TECHNOTRONIK LiYY-P are multipair control cables intended for control and instrumentation circuits, for signal, monitoring and data processing systems and for analogue or digital data transmission, all for industrial electronic applications.
Paired structure decreases mutual influence between signals transmitted along the cable and reduces influence of outer sources of interference.
The cables are designed to offer high flexibility and small outer diameter combined with tensile strength.
The cables can also be used for power supply to small auxiliary devices on condition that current-carrying capacity limit (see our Technical Guide) is not exceeded.
The cables are suitable for indoor installations connecting fixed and movable equipment.
Cable outer sheath is oil-resistant.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,
- PVC insulation - identification colour code in accordance with DIN VDE 47100,
- insulated conductors twisted into pairs,
- pairs laid-up in layers,
- cable core wrapped in polyester tape,
- PVC cable sheath, grey RAL 7001, other colours also available.
AVAILABLE UPON REQUEST
TECHNOTRONIK LiYY-P-O - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN-EN 60811-404.
TECHNOTRONIK LiY11Y-P - polyurethane sheathed cables of enhanced protection against mechanical damage, particularly to abrasion and tear, also resistant to oils, petrol, bacteria and ultraviolet radiation.
TECHNOTRONIK LiHH-P - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.
TECHNOTRONIK IB-LiYY-P - specially designed intrinsically safe cable.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.14 |
0.25 |
0.34 |
0.5 |
0.75 |
1.0 |
1.5 |
Operating voltage peak value |
V |
350 |
350 |
350 |
500 |
500 |
500 |
500 |
Voltage test |
V rms |
1200 |
1200 |
1200 |
1500 |
1500 |
1500 |
1500 |
DC loop resistance at 20°C, maximum |
Ω/km |
288.0 |
158.0 |
114.0 |
78.0 |
52.0 |
39.0 |
26.6 |
Mutual capacitance at 1 kHz, approximate |
nF/km |
90 |
90 |
100 |
100 |
120 |
120 |
130 |
Operating voltage Uo/U Insulation resistance, minimum Inductance, approximate Impedance, approximate Capacitance unbalance, maximum |
300/300 V 20 MΩ·km 0.7 mH/km 80 Ω 300 pF/100 m |
Operating temperature range for fixed installation for movable installation Minimum bending radius Cable combustibility Combustibility tests Reference standards |
from - 30 to + 80°C from - 5 to + 70°C 7.5 x cable diameter flame retardant PN-EN 60332-1-2, IEC 60332-1-2 DIN VDE 0812, DIN VDE 0814 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and pair counts available on request.