FLEXIBLE HOOK-UP WIRES | Technical Data sheet |
|
|
APPLICATIONS
LiY and LiYV are hook-up wires intended for use in remote control, signal and data transmission and industrial data processing systems and computer networks.
Generally, they are designed for control cabinets, electronic devices and others as interconnection cables for electronic modules, equipment and instruments.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (LiY) or tinned copper wires (LiYV),
- PVC insulation - coloured according to customer’s requirement.
AVAILABLE UPON REQUEST
LiH - halogen free wires, applied when higher safety in case of fire is required. The wires are flame retardant, their smoke emission in fire is low and released gases are not corrosive.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.14 |
0.25 |
0.34 |
0.5 |
0.75 |
1.0 |
1.5 |
2.5 |
Operating voltage peak value |
V |
350 |
350 |
350 |
500 |
500 |
500 |
500 |
500 |
Voltage test |
V rms |
1200 |
1200 |
1200 |
1500 |
1500 |
1500 |
1500 |
1500 |
DC conductor resistance at 20°C, maximum |
Ω/km |
|
|
|
|
|
|
|
|
bare copper wire |
|
144.0 |
79.0 |
57.0 |
39.0 |
26.0 |
19.5 |
13.3 |
7.98 |
tinned copper wire |
|
148.0 |
82.0 |
59.0 |
40.1 |
26.7 |
20.0 |
13.7 |
8.21 |
Operating voltage Insulation resistance, minimum Operating temperature range for fixed installation for movable installation |
300/300 V 20 MΩ·km from - 30 to + 70°C from - 5 to + 70°C
|
Minimum bending radius Wire combustibility Combustibility tests
Reference standards |
7.5 x wire diameter flame retardant PN-EN 60332-1-2, IEC 60332-1-2 PN-EN 60332-2-2, IEC 60332-2-2 DIN VDE 0812, DIN VDE 0814 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other conductor cross-sections available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.