FLEXIBLE HOOK-UP WIRES Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

LiY and LiYV are hook-up wires intended for use in remote control, signal and data transmission and industrial data processing systems and computer networks.

Generally, they are designed for control cabinets, electronic devices and others as interconnection cables for electronic modules, equipment and instruments.

CONSTRUCTION

- flexible, multiwire conductors, stranded of bare annealed copper wires (LiY) or tinned copper wires (LiYV),

- PVC insulation  - coloured according to customer’s requirement.

AVAILABLE UPON REQUEST

LiH - halogen free wires, applied when higher safety in case of fire is required. The wires are flame retardant, their smoke emission in fire is low and released gases are not corrosive.

CHARACTERISTICS

Conductor cross-section

mm2

0.14

0.25

0.34

0.5

0.75

1.0

1.5

2.5

Operating voltage peak value

V

350

350

350

500

500

500

500

500

Voltage test

V rms

1200

1200

1200

1500

1500

1500

1500

1500

DC conductor resistance at 20°C, maximum

Ω/km

 

 

 

 

 

 

 

 

bare copper wire

 

144.0

79.0

57.0

39.0

26.0

19.5

13.3

7.98

tinned copper wire

 

148.0

82.0

59.0

40.1

26.7

20.0

13.7

8.21

 

Operating voltage

Insulation resistance, minimum

Operating temperature range

            for fixed installation

            for movable installation

 

300/300 V

20 MΩ·km

from - 30 to + 70°C

from   - 5 to + 70°C

 

Minimum bending radius

Wire combustibility

Combustibility tests

 

Reference standards

7.5 x wire diameter

flame retardant

PN-EN 60332-1-2, IEC 60332-1-2

PN-EN 60332-2-2, IEC 60332-2-2

DIN VDE 0812, DIN VDE 0814

 

The cable meets requirements of the low voltage directive 2014/35/EU

Other conductor cross-sections available on request.