INTRINSICALLY SAFE CABLES | Technical Data sheet |
|
|
APPLICATIONS
TECHNOKONTROL IB1-YSLY are cables intended for intrinsically safe circuits and explosive conditions zones, designed for operating voltage 0.6/1 kV.
The cables are designed to offer high flexibility combined with tensile strength.
Sheathing PVC of high oxygen index is UV radiation and weather resistant, is self-extinguishing and flame retardant. The cables pass combustibility test according to PN-EN 60332-3 standard.
The cables are oil-resistant and designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled.
The cables are suitable for fixed indoor installations.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 2 per PN-EN 60228,
- black PVC insulation and white conductor numbers printed on it for identification,
- insulated conductors laid-up in layers,
- oil, petrol and UV radiation resistant and self-extinguishing (oxygen index bigger than 29%) PVC cable sheath, blue RAL 5015 according to VDE 0165 6.1.3.2.3.
AVAILABLE UPON REQUEST
TECHNOKONTROL IB1-YSLYv - intrinsically safe cables with enhanced PVC sheath, suitable for outdoor installations and direct earth burial.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.5 |
0.75 |
1.0 |
1.5 |
2.5 |
DC conductor resistance at 20°C, maximum |
Ω/km |
36.0 |
24.5 |
18.1 |
12.1 |
7.41 |
Capacitance between conductors at 1 kHz, appr. |
nF/km |
100 |
110 |
120 |
130 |
140 |
Operating voltage Uo/U Voltage test Insulation resistance, minimum Inductance, approximate |
0.6/1 kV 3.5 kV rms 20 MΩ·km 0.7 mH/km |
Operating temperature range for fixed installation for movable installation Minimum bending radius Cable combustibility Combustibility tests Oil resistance |
from - 30 to + 80°C from - 5 to + 70°C 7.5 x cable diameter flame retardant PN-EN 60332-1-2, IEC 60332-1-2 PN-EN 60811-404 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.