XLPE INSULATED AND HALOGEN FREE SHEATHED CONTROL CABLES Technical Data sheet
 DoP

 

 acrobat reader_50x50  acrobat reader_50x50

APPLICATIONS

N2XH-O B2ca 0,6/1 kV and N2XH-J B2ca 0,6/1 kV power cables are designed for electric power transmission. They are also applied in control, protection and monitoring systems in power engineering.

The cables are suitable for industrial applications, such as production plants or air-conditioning systems operating in dry and wet locations, also for outdoor installations. Cables can be laid in concrete. Laying cables in water or direct earth burial is only permitted if additional protection is used.

Halogen free cables shall be applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required. The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive.

CONSTRUCTION                                                                                                           

- bare annealed copper conductors meeting requirements of PN-EN 60228 standard:

              RE - class 1 circular single-wire,

              RM - class 2 circular multi-wire.

- cross-linked polyethylene (XLPE) insulation, colours:

              in accordance with PN-HD 308 standard,

              or black and white conductor number printed on it;

              green-yellow protective conductor in the outer layer in N2XH-J B2ca 0,6/1 kV cable,

- insulated conductors laid-up into a cable core,

- inner covering made of halogen free compound (HFFR),

- cable sheath made of halogen free compound (HFFR), black, other colours also available.

CHARACTERISTICS

Conductor cross-section

mm2

1,5

2,5

4

6

10

16

25

35

DC conductor resistance at 20°C, maximum

Ω/km

12.1

7.41

4.61

3.08

1.83

1.15

0.727

0.524

Conductor cross-section

mm2

50

70

95

120

150

185

240

 

DC conductor resistance at 20°C, maximum

Ω/km

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

 

 

Operating voltage Uo/U

0.6/1 kV

Voltage test

4 kV rms

Insulation resistance, minimum

100 MΩ·km

Corrosivity of emitted gases per

PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2

pH appr.

6,8

conductivity appr.

0,4 µS/mm

Smoke density per

PN-EN 61034-2, IEC 61034-2

minimum light transmittance

60%

Conductor temperature limit

in work conditions

+90°C

in short-circuit

+250°C

Operating temperature range

during operation

from -30 to +90°C

during installation

from -5 to +50°C

Minimum bending radius

12 x cable diameter

Cable combustibility

flame retardant

Combustibility tests

PN-EN 50399, PN-EN 60332-1-2, IEC 60332-1-2
>= 25 mm2

PN-EN 60332-3-23, IEC 60332-3-23 (cat. B)

< 25 mm2 PN-EN 60332-3-24, IEC 60332-3-24 (cat. C)

Reference standards

PN-HD 604 S1, IEC 60502-1, DIN VDE 0276 part 604

CPR – reaction to fire

B2ca – s1b,d0,a1 (acc. to PN-EN 50575)

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.