CONTROL AND POWER SUPPLY CABLESS | Technical Data sheet |
|
|
APPLICATIONS
TECHNOKONTROL YSLCY-P-Nr-O (9) 0,6/1 kV are multipair overall shielded cables intended for control, protection and monitoring systems or power supply, all in power engineering. The cables are also intended for wiring industrial plants, such as production lines, air-conditioning equipment etc.
Paired structure decreases mutual influence between signals transmitted along the cable.
The overall shield protects the cables against external electromagnetic interferences and prevents emission of interferences produced in the cables.
The cables are designed to offer high flexibility combined with tensile strength.
Sheathing PVC of high oxygen index is UV radiation and weather resistant, is self-extinguishing and flame retardant. The cables pass combustibility test according to PN-EN 60332-3 standard.
The cables are oil-resistant and designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled.
The cables are suitable for fixed indoor and outdoor installations.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 2 per PN-EN 60228,
- PVC insulation, identification of pairs:
”a” wire – black insulation and white pair number printed on it,
”b” wire – white insulation and black pair number printed on it,
- insulated conductors twisted into pairs,
- pairs laid-up in layers into a cable core,
- cable core wrapped in polyester tape,
- tinned copper wire braid shield of effective density coverage,
- cable screen wrapped in polyester tape,
- oil, petrol and UV radiation resistant and self-extinguishing (oxygen index bigger than 29%) PVC cable sheath, black RAL 9005, other colours also available.
AVAILABLE UPON REQUEST
TECHNOKONTROL YSLCYv-P-Nr-O (9) 0,6/1 kV - cables with enhanced PVC sheath, suitable for direct earth burial.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.5 |
0.75 |
1.0 |
1.5 |
2.5 |
DC loop resistance at 20°C, maximum |
W/km |
72.0 |
49.0 |
36.2 |
24.2 |
14.82 |
Mutual capacitance at 1 kHz, approximate |
nF/km |
120 |
120 |
120 |
130 |
140 |
Operating voltage Uo/U Voltage test Insulation resistance, minimum Inductance, approximate |
0.6/1 kV 3.5 kV rms 20 MΩ·km 0.7 mH/km |
Operating temperature range for fixed installation for movable installation Minimum bending radius Cable combustibility Combustibility tests Oil resistance |
from - 30 to + 80°C from - 5 to + 70°C 10 x cable diameter flame retardant PN-EN 60332-1-2, IEC 60332-1-2 PN-EN 60811-404 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and pair counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.