CONTROL CABLES FOR INDUSTRIAL ELECTRONIC APPLICATIONS | Technical Data sheet |
|
|
APPLICATIONS
TECHNOTRONIK LiYwYw 105°C are heat resistant control cables intended for control and instrumentation circuits, for signal, monitoring and data processing systems and for analogue or digital data transmission, all for industrial electronic applications.
The cable can be applied at higher operating temperatures up to 105°C due to insulation and sheath made of special heat resistant PVC.
The cables are designed to offer high flexibility and small outer diameter combined with tensile strength.
The cables can also be used for power supply to small auxiliary devices on condition that current-carrying capacity limit (see our Technical Guide) is not exceeded.
The cables are suitable for indoor installations connecting fixed and movable equipment.
Cable outer sheath is oil-resistant.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,
- heat resistant PVC insulation, identification colour code in accordance with DIN VDE 47100,
- insulated conductors laid-up into a cable core,
- special heat resistant PVC cable sheath, grey (RAL 7001), other colours also available.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.14 |
0.22 |
0.35 |
0.5 |
0.75 |
1.0 |
1.5 |
Operating voltage, peak value |
V |
350 |
350 |
350 |
500 |
500 |
500 |
500 |
Voltage test |
V rms |
1200 |
1200 |
1200 |
1500 |
1500 |
1500 |
1500 |
DC conductor resistance at 20°C, maximum |
Ω/km |
144.0 |
90.0 |
57.0 |
39.0 |
26.0 |
19.5 |
13.3 |
Capacitance between conductors at 1 kHz, appr. |
nF/km |
90 |
100 |
110 |
110 |
110 |
120 |
120 |
Operating voltage Uo/U Insulation resistance, minimum Inductance, approximate Impedance, approximate |
300/300 V 20 MΩ·km 0.7 mH/km 80 Ω |
Operating temperature range for fixed installation for movable installation Minimum bending radius Cable combustibility Combustibility tests Reference standards |
from - 40 to + 105°C from - 5 to + 90°C 7.5 x cable diameter flame retardant PN-EN 60332-1-2, IEC 60332-1-2 DIN VDE 0812, DIN VDE 0814 |
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.