DATA TRANSMISSION CABLE | Technical Data sheet |
|
|
APPLICATIONS
J-2Y(St)(St)Y 120 Ω are multipair, pair and overall shielded cables intended for control and instrumentation circuits, for signal, monitoring and data processing systems and for analogue or digital data transmission, all in industrial electronics applications.
Cables are designed for transmission in ISDN, PCM, RS 232, RS 422, RS 423, Ethernet 10baseT 10 Mb/s, Token Ring 4/16 Mb/s systems.
Shielded pair structure substantially decreases mutual influence between signals transmitted along the cable.
The cable is protected by an overall electrostatic shield against external electric interferences and prevents emission of interferences produced in the cable.
The cables are suitable for fixed indoor installations.
CONSTRUCTION
- annealed tin-plated copper single wire round conductors of diameter 0.4 mm,
- polyethylene (PE) insulation - identification colour code according to PN-92/T-90321,
- insulated conductors twisted into pairs,
- pair electrostatic shield incorporating a plastic laminated metal foil and an annealed tinned copper single drain wire,
- shielded pairs laid-up into a cable core,
- overall electrostatic shield incorporating a plastic laminated metal foil and an annealed tinned copper single drain wire,
- PVC cable sheath, grey RAL 7001, other colours also available.
AVAILABLE UPON REQUEST
J-2Y(St)(St)H 120 Ω - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.
CHARACTERISTICS
Characteristic impedance Mutual capacitance at 1 kHz Insulation resistance, minimum Attenuation loss, [dB/100m] max - at frequency [MHz]: 1 4 10 16 |
120 ± 15 Ω 50 ± 5 nF/km 10 GΩ·km
3.6 6.0 9.0 11.0 |
Operating voltage Voltage test DC loop resistance at 20°C, maximum Operating temperature range during operation during installation Minimum bending radius Cable combustibility Combustibility tests Reference standards |
150 V 1500 V rms 290 Ω/km
from -30 to +70 °C from -5 to +50 °C 15 x cable diameter flame retardant PN-EN 60332-1-2, IEC 60332-1-2 DIN VDE 815 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other diameters and pair counts available on request.