CONTROL AND POWER SUPPLY FLEXIBLE CABLES | Technical Data Sheet |
|
|
APPLICATIONS
YSLCY-JZ 0,6/1 kV, YSLCY-OZ 0,6/1 kV, YSLCY-JB 0,6/1 kV and YSLCY‑OB 0,6/1 kV are flexible, overall shielded cables intended for control, protection and monitoring systems or power supply, all in power engineering. The cables are also intended for wiring industrial plants, such as production lines, air-conditioning equipment etc.
The overall shield protects the cables against external electromagnetic interferences and prevents emission of interferences produced in the cables.
The cables are designed to offer high flexibility combined with tensile strength.
The cables are suitable for indoor and outdoor installations in dry and wet locations, also for direct earth burial.
Sheathing black PVC is resistant to UV radiation.
Cable outer sheath is oil-resistant.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,
- PVC insulation - identification colour code:
YSLCY-OZ 0,6/1 kV - black and white conductor number printed on it,
YSLCY‑OB 0,6/1 kV - colours in accordance with PN-HD 308 standard, green-yellow protective conductor located in the outer layer in YSLCY-JZ 0,6/1 kV and YSLCY-JB 0,6/1 kV cable,
- insulated conductors laid-up in layers,
- cable core wrapped in polyester tape,
- tinned copper wire braid shield of effective density coverage,
- black (RAL 9005) PVC cable sheath, other colours also available.
AVAILABLE UPON REQUEST
YSLCY-JZ OR 0,6/1 kV, YSLCY-OZ OR 0,6/1 kV, YSLCY-JB OR 0,6/1 kV and YSLCY‑OB OR 0,6/1 kV - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN-EN 60811-404.
HSLCH-JZ 0,6/1 kV, HSLCH-OZ 0,6/1 kV, HSLCH-JB 0,6/1 kV and HSLCH‑OB 0,6/1 kV - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.5 |
0.75 |
1.0 |
1.5 |
2.5 |
4.0 |
DC conductor resistance at 20°C, maximum |
Ω/km |
39.0 |
26.0 |
19.5 |
13.3 |
7.98 |
4.95 |
Conductor cross-section |
mm2 |
6.0 |
10 |
16 |
25 |
35 |
50 |
DC conductor resistance at 20°C, maximum |
Ω/km |
3.30 |
1.91 |
1.21 |
0.780 |
0.554 |
0.386 |
Operating voltage Uo/U Voltage test Insulation resistance, minimum Conductor temperature limit in work conditions at short-circuit |
0.6/1 kV 4 kV rms 20 MΩ·km
+ 70°C + 160°C |
Operating temperature range for fixed installation for movable installation Minimum bending radius Cable combustibility Combustibility tests Reference standards |
from - 40 to + 80°C from - 5 to + 70°C 10 x cable diameter flame retardant PN-EN 60332-1-2, IEC 60332-1-2 WT-TK-50 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.