MINING POWER CABLES Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

YnKGSLYżo-P (multipair) and YnKGSLYżo-T (multitriple) are mining control cables intended for control, communication, measuring and monitoring systems in mines.

Cables can be applied in:

- opencast and underground mines, except explosive condition zones.

- underground mines in their non-methane and methane fields in areas of „a” degree explosion hazard.

- underground mines in workings of class A coal dust explosion hazard.

- intrinsically safe circuits in opencast and underground mines in explosion hazardous areas.

- intrinsically safe circuits in underground mines in areas classified as „a”, „b”, or „c” degree explosion hazard.

Cables can not be used for power supplying in power engineering installations.

Paired or tripled structure decreases mutual influence between signals transmitted along the cable and reduces influence of outer sources of interference.

Cables have positive Technical Opinion No. 05/53 regarding application in underground mines and Certificate No. 05/53/A1/2 issued by TI EMAG Institute.

CONSTRUCTION                                                                                                           

-  flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,

-  PVC insulation, identification colour code:

                   pairs – black and brown insulation and white pair number printed on it,

                   triples – black, brown and blue insulation and white triple number printed on it,

- insulated conductors twisted into pairs or triples,

- pairs or triples laid-up in layers into a cable core,  green-yellow protective conductor located in the outer layer, cables are made of  2, 3, 4, 5, 7, 8, 10, 12, 14, 15, 16, 18, 19, 21, 24, 25, 28, 30, 40 and 50 pairs or triples,

- cable core wrapped in polyester tape,

- special (oxygen index bigger than 29%) PVC cable sheath, black (RAL 9005) or blue (RAL 5015 – for intrinsically safe circuits), other colors also available.

AVAILABLE UPON REQUEST

YnKGSLXżo-P, YnKGSLXżo-T - polyethylene insulated cables (X) of low capacitance, designed to transmit signals over long distances. Cables are designed for operating voltage 300/300 V. Cable sheath made of special self-extinguishing and flame retardant PVC (Yn).

XnKGSLXżo-P, XnKGSLXżo-T - halogen free cables of reduced combustibility, sheathed with special halogen free material (Xn), applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive. Cables are designed for operating voltage 300/300 V.

CHARACTERISTICS

Conductor cross-section

mm2

0.5

0.75

1.0

1.5

2.5

DC conductor resistance at 20°C, maximum

Ω/km

78.0

52.0

39.0

26.6

16.0

 

Operating voltage Uo/U

V

300/300

300/500

600/1000

Voltage test

V rms

1500

3000

3500

Insulation resistance, minimum

MΩ·km

20

20

100

Inductance, approximate    0.7 mH/km

Conductor temperature limit
      in work conditions          - 30 to + 70°C
      in short-circuit               - 5 to + 70°C

Minimum bending radius      10 x cable diameter

Cable combustibility            flame retardant

Combustibility tests             PN-EN 60332-1-2, IEC 60332-1-2, PN-EN 60332-3-24, IEC 60332-3-24 (cat. C)

Reference standards           WT-TK-24

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.