PVC INSULATED AND SHEATHED POWER CABLES Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

NYY-O 0,6/1 kV and NYY-J 0,6/1 kV power cables are designed for electric power transmission. They are also applied in power circuits in industrial plants and power stations and in local distribution networks.

The cables are suitable for indoor and outdoor installations, for laying in cable ducts and for direct earth burial.

CONSTRUCTION                                                                                                          

- bare annealed copper conductors meeting requirements of PN-EN 60228 standard:

              RE - class 1 circular single-wire,

              RM - class 2 circular multi-wire,

              SM - class 2 sector shaped multi-wire,

- PVC insulation – colours:

               in accordance with PN-HD 308 standard,

               or black and white conductor number printed on it,

              green-yellow protective conductor in NYY-J 0,6/1 kV and NYY-JZ 0,6/1 kV cable,

- insulated conductors laid-up in layers,

- inner covering,

- black PVC cable sheath, other colours also available.

AVAILABLE UPON REQUEST

N2XY-O 0,6/1 kV and N2XY-J 0,6/1 kV - cross-linked polyethylene (XLPE) insulated and PVC sheathed power cables with better electric performances, smaller dimensions and weight in relation to the PVC insulated cables.

N2XH-O 0,6/1 kV and N2XH-J 0,6/1 kV - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.

Steel wire or steel tape armoured cables as above applied in locations where enhanced protection against mechanical damages is required.

 

CHARACTERISTICS

Conductor cross-section

mm2

1,5

2,5

4

6

10

16

25

35

DC conductor resistance at 20°C, maximum

Ω/km

12.1

7.41

4.61

3.08

1.83

1.15

0.727

0.524

Conductor cross-section

mm2

50

70

95

120

150

185

240

300

DC conductor resistance at 20°C, maximum

Ω/km

0.387

0.268

0.193

0.153

0.124

0.0991

0.0754

0.0601

Operating voltage Uo/U    0.6/1 kV

Voltage test    4 kV rms

Insulation resistance, minimum    20 MΩ·km

Conductor temperature limit

      in work conditions          +70°C
      in short-circuit               +160°C

Temperature range
      during operation            from - 30 to + 70°C
      during installation          from   - 5 to + 50°C

Minimum bending radius

      single wire cables           15 x cable diameter

      multi wire cables            12 x cable diameter

Cable combustibility              flame retardant

Combustibility tests               PN-EN 60332-1-2, IEC 60332-1-2

Reference standards             PN-HD 603 S1, DIN VDE 0276 part 603, IEC 60502-1

 

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.