CABLES FOR ALARM AND SECURITY SYSTEMS Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

YTDYekw are overall shielded cables intended for low-voltage circuits, such as remote control, signal and data transmission systems. Also suitable for interconnecting wiring in telephony, alarm and security systems.

The cable is protected by an overall electrostatic shield against external electric interferences and prevents emission of interferences produced in the cable.

The cables are suitable for fixed indoor installations.

CONSTRUCTION

- annealed copper single wire round conductors of diameter 0.5 mm,

- PVC insulation - identification colour code in accordance with Technokabel’s Identification System (see our Technical Guide),

- insulated conductors laid-up into a cable core,

- overall shield incorporating aluminium-polyester tape and annealed tinned copper single drain wire,

- PVC cable sheath, white RAL 9010, other colours also available.

CHARACTERISTICS

Conductor diameter

DC conductor resistance at 20°C, maximum

Operating voltage

Voltage test

      AC voltage for 60s

      DC voltage

Insulation resistance, minimum

0.5 mm

97.8 Ω/km



150 V

1000 V rms

1500 V

200 MΩ·km

Inductance, approximate

Operating temperature range

      during operation

      during installation

Minimum bending radius

Cable combustibility

Combustibility tests

Reference standards

0,7 mH/km

 

from - 30 to + 70°C

from   - 5 to + 50°C

10 x cable diameter

flame retardant

PN-EN 60332-1-2, IEC 60332-1-2

PN-92/T-90203, PN-92/T-90200

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.