MOTOR SUPPLY CABLES Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

TECHNOFLEX 2YSLCY-J and TECHNOFLEX 2YSLCYK-J  shielded cables are intended for connecting converters or inverters with motors in industrial installations, production plants, air-conditioners and other equipment operating in dry and wet locations.

Cables are protected by a specially designed and highly effective collective shield against emission of electromagnetic interferences to environment and against influence of external interferences.

TECHNOFLEX 2YSLCY-J cables are suitable for indoor and TECHNOFLEX 2YSLCYK-J cables for outdoor fixed and movable installations.

Cable outer sheath is oil-resistant.

CONSTRUCTION

- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,

- polyethylene (PE) insulation - black, blue, brown and green-yellow,

- insulated conductors laid-up in a cable core,

- double screen of aluminium laminated tape and braid of tinned copper wire, braid shield of coverage bigger than 80%,

- PVC cable sheath of TECHNOFLEX 2YSLCY-J cable, transparent or grey RAL 7001, other colours also available,

- PVC cable sheath of TECHNOFLEX 2YSLCYK-J cable, black RAL 9005, other colours also available.

AVAILABLE UPON REQUEST

TECHNOFLEX 2YSLCH-J - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.

 

CHARACTERISTICS

Operating voltage Uo/U    0.6/1 kV

Voltage test    2.5 kV rms

Insulation resistance, minimum    200 MΩ·km

Shielding efficiency, approximate      75 dB

Conductor temperature limit
     in work conditions                  + 70°C

Effective capacitance (according to different cross-sections)

      conductor/conductor    70 to 250 nF/km

      conductor/screen         110 to 410 nF/km

Operating temperature range

for fixed installation              from - 40 to + 70°C
for movable installation         from  + 5 to + 70°C

Minimum bending radius

   static for diameters:

                  up to 12 mm         5 x cable diameter

           from 12 to 20 mm         7.5 x cable diameter

                   from 20 mm         10 x cable diameter

   flexible for diameters:

                  up to 12 mm         10 x cable diameter

           from 12 to 20 mm         15 x cable diameter

                   from 20 mm          20 x cable diameter

Cable combustibility      flame retardant

Combustibility tests      PN-EN 60332-1-2, IEC 60332-1-2

Reference standards    DIN VDE 0250

 

The cable meets requirements of the low voltage directive 2014/35/EU

 

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.