CONTROL AND POWER SUPPLY FLEXIBLE CABLES Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

TECHNOFLEKS LiYwYw 105ºC 0,6/1 kV and TECHNOFLEKS LiYwYwżo 105ºC 0,6/1 kV are flexible heat resistant cables designed for wet or dry locations and intended for control, protection and monitoring systems or power supply, all in power engineering. The cables are also intended for wiring industrial plants, such as production lines, air-conditioning equipment etc.

The cable can be applied at higher operating temperatures up to 105°C due to insulation and sheath made of special heat resistant PVC.

The cables are designed to offer high flexibility combined with tensile strength.

The cables are suitable for indoor installations connecting fixed and movable equipment.

Cable outer sheath is oil-resistant.

CONSTRUCTION                                                                                                           

- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,

- heat resistant PVC insulation - identification colour code in accordance with Technokabel’s Identification System (see our Technical Guide),

- insulated conductors laid-up in layers, green-yellow protective conductor located in the outer layer in TECHNOFLEKS LiYwYwżo 105ºC 0,6/1 kV cable,

- special heat resistant PVC cable sheath, grey (RAL 7001), other colours also available.

CHARACTERISTICS

Conductor cross-section

mm2

1.5

2.5

4.0

6.0

10.0

DC conductor resistance at 20°C, maximum

Ω/km

13.3

7.98

4.95

3.30

1.91

 

Operating voltage Uo/U

Voltage test

Insulation resistance, minimum

Conductor temperature limit

        in work conditions

        at short-circuit

0.6/1 kV

3.5 kV rms

20 MΩ·km

 

+ 90°C

+160°C

Operating temperature range

      for fixed installation

      for movable installation

Minimum bending radius

Cable combustibility

Combustibility tests

Reference standards

 

from - 40 to + 105°C

from   - 5 to + 90°C

7.5 x cable diameter

flame retardant

PN-EN 60332-1-2, IEC 60332-1-2

DIN VDE 0245, DIN VDE 0250,

DIN VDE 0281

 

 The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.