PVC INSULATED AND SHEATHED POWER CABLES WITH CONCENTRIC CONDUCTOR Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

NYCY 0,6/1 kV power cables are designed for electric power transmission. They are also applied in control, protection and monitoring systems in power engineering.

The cables are suitable for industrial applications, such as production plants or air-conditioning systems operating in dry and wet locations, also for outdoor installations, in cable ducts or for direct earth burial.

CONSTRUCTION                                                                                                          

- bare annealed copper conductors meeting requirements of PN-EN 60228 standard:

              RE - class 1 circular single-wire,

              RM - class 2 circular multi-wire,

              SM - class 2 sector shaped multi-wire,

- PVC insulation – colours:

               to 5 wires in accordance with PN-HD 308 S2 standard,

               above 5 wires in accordance with EN 50334 standard,

- insulated conductors laid-up in layers,

- inner covering,

- concentric conductor formed by bare copper wires with counter helix of copper tape,

- polyester tape,

- black PVC cable sheath, other colours also available.

 

AVAILABLE UPON REQUEST

N2XCH 0,6/1 kV - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.

NHXCH FE180 PH90/E30-E90 0,6/1 kV – fire-resistant power cables with halogen free insulation and sheath, intended for fire devices, operating in case of a fire (e.g. for supplying water pumps, smoke removal fans).

 

CHARACTERISTICS

Conductor cross-section

mm2

1,5

2,5

4

6

10

16

25

35

DC conductor resistance at 20°C, maximum

Ω/km

12.1

7.41

4.61

3.08

1.83

1.15

0.727

0.524

 

Operating voltage Uo/U    0.6/1 kV

Voltage test    4 kV rms

Insulation resistance, minimum    20 MΩ·km

Conductor temperature limit

      in work conditions          +70°C
      in short-circuit               +160°C

Temperature range
      during operation            from - 30 to + 70°C
      during installation          from   - 5 to + 50°C

Minimum bending radius

      single wire cables           15 x cable diameter

      multi wire cables            12 x cable diameter

Cable combustibility              flame retardant

Combustibility tests               PN-EN 60332-1-2, IEC 60332-1-2

Reference standards             PN-HD 603 S1, DIN VDE 0276 part 603, IEC 60502-1

 

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.