FIRE RESISTANT HALOGEN FREE CABLES Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

TECHNOFLAME HTKSHekw FE180 PH90/E30-E90 fire resistant and halogen free screened cables are intended for installation in alarm, signalling, transmission, sound warning and similar systems, also for data processing systems and for analogue or digital data transmission in industrial electronics and control applications in objects of sharp fire protection requirements, particularly in fire alarm and fire automatic control systems.

The cables are certified by Scientific and Research Development Centre for Fire Protection (Centrum Naukowo-Badawcze Ochrony Przeciwpożarowej - PIB) at Józefów.

Cable circuits are protected by an overall electrostatic shield against external electric field interferences.

Halogen free cables are applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required. 

Functions of the cables are maintained – data are transmitted and power is supplied to equipment which must operate in fire conditions and during fire fighting (e.g. emergency lighting). The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive.

The cables are resistant to water in accordance with the standard PN-EN 50200 Annex E and can be used in fire protected rooms with fixed pressure water spraying  fire extinguishing systems (sprinkler zones).

The cables are suitable for indoor installations.

 

CONSTRUCTION                                                                                                           

conductor        –          bare copper, solid,

insulation        –          mica tape and halogen free compound insulation - colours in accordance with IEC 60189-2 and PN-92/T-90321 standards,

pair                  –          insulated conductors twisted into pairs,

cable core        –          pairs laid-up into a cable core,

separator         –          polyester tape,

shielding         –          overall electrostatic shield incorporating a plastic laminated metal foil and a tinned copper drain wire,

sheath              –          red, cable sheath made of halogen free compound according to EN 50290-2-27 and VDE 0250-214 – HM2.

 

 

CHARACTERISTICS

Cable type

 

HTKSHekw FE180 PH90/E30-E90

 

 

Conductor diameter

mm

0.8

1.0

1.4

1.8

2.3

2.8

 

Conductor cross-section

mm2

0.5

0.75

1.5

2.5

4

6

 

DC loop resistance at 20°C, maximum

Ω/km

75

48

24.5

14.9

9.3

6.3

 

Capacitance between conductors at 1 kHz

maximum

nF/km

100

100

130

130

130

140

 

 

average

80

90

110

120

120

130


Operating voltage:    240 V

Voltage test:    1.5 kV rms

Insulation resistance, minimum:    500 MΩ·km

Inductance, approximate:    0.7 mH/km

Corrosivity  of emitted gases per:    PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2

pH:    >4.3

conductivity:    <2.5 µS/mm

Smoke density per:    PN-EN 61034-2, IEC 61034-2

light transmittance, minimum:    80%

Operating temperature range:

      during operation                  from - 30 to + 80°C
      during installation                 from   - 5 to + 70°C

Minimum bending radius:              10 x cable diameter

Cable combustibility:                    flame retardant

Combustibility tests:                    PN-EN 60332-1-2, IEC 60332-1-2, PN-EN 60332-3-24, IEC 60332-3-24 (cat. C)

Circuit integrity * :                         

             E30-E90                      DIN 4102-12

             PH120                       PN-EN 50200+Annex E

Insulation integrity  FE180:          IEC 60331-21; IEC 60331-11

Reference standards:                  CNBOP-PIB-KOT-2021/0296-3701 wyd.1; WT-TK-43

Class reaction to fire (according to PN-EN 13501-6):  B2ca-s1b,d0,a1

*Circuit integrity is dependent on installation method.

Cable installation - should be carried out on a certified cable fastening system, in accordance with the National Technical Assessments (KOT) or Technical Approvals (AT) issued for fastening manufacturers. Only certified cable fixing systems, tested according to DIN 4102 part 12, should be used.

 

The cable meets requirements of the low voltage directive 2014/35/EU


TECHNOKABEL S.A. reserves the right to change specifications without prior notice.