HALOGEN FREE CONTROL CABLES FOR INDUSTRIAL ELECTRONIC APPLICATIONS | Technical Data sheet |
|
|
APPLICATIONS
TECHNOTRONIK LiHH are halogen free control cables intended for control and instrumentation circuits, for signal, monitoring and data processing systems and for analogue or digital data transmission, all for industrial electronic applications.
Halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.
The cables are designed to offer high flexibility and small outer diameter combined with tensile strength.
The cables are suitable for connecting fixed and movable equipment inside rail vehicles, subway trains, in trams, as well as for indoor installations.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,
- insulation made of halogen free compound (HFFR) - identification colour code in accordance with DIN VDE 47100,
- insulated conductors laid-up in layers,
- cable sheath made of halogen free compound (HFFR), grey (RAL 7001), other colours also available.
AVAILABLE UPON REQUEST
TECHNOTRONIK IB-LiHH - specially designed intrinsically safe cable.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.5 |
0.75 |
1.0 |
1.5 |
2.5 |
DC conductor resistance at 20°C, maximum |
Ω/km |
39.0 |
26.0 |
19.5 |
13.3 |
7.98 |
Capacitance between conductors at 1 kHz, appr. |
nF/km |
80 |
90 |
100 |
120 |
140 |
Operating voltage Uo/U |
300/300 V |
Insulation resistance, minimum |
20 MΩ·km |
Voltage test |
1.5 kV rms |
Inductance, approximate |
0.7 mH/km |
Impedance, approximate |
80 Ω |
Corrosivity of emitted gases per |
PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2 |
Operating temperature range |
|
for fixed installation |
from - 30 to + 70°C |
for movable installation |
from - 5 to + 70°C |
Minimum bending radius |
7.5 x cable diameter |
pH, appr. |
6,8 |
conductivity appr. |
0,4 µS/mm |
Smoke density |
PN-EN 61034-2, IEC 61034-2 |
light transmittance, min |
70% |
Cable combustibility |
flame retardant |
Combustibility tests |
PN-EN 60332-1-2, IEC 60332-1-2 |
Reference standards |
DIN VDE 0812, DIN VDE 0814 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.