TELECOMMUNICATION CABLES Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

XzTKSXwekp 120 16x(1x2x0.4c) mm are multipair, pair inividually shielded cables intended for control and instrumentation circuits, for signal, monitoring and data processing systems and for analogue or digital data transmission, all in industrial electronics applications.

Cables provide data transmission in the following systems: ISDN, PCM and others.

Shielded pair structure substantially decreases mutual influence between signals transmitted along the cable.

Moisture barrier is made of plastic laminated aluminium tape longitudinally applied over a cable core and bonded to polyethylene (PE) cable sheath. The cable core is filled with petro-gel to protect the cable against moisture penetration along the cable.

Sheathing polyethylene (PE) is halogen free and UV radiation and weather resistant, however, it is not self-extinguishing and flame retardant.

The cable is suitable for outdoor installations, laying in ducts and direct earth burial.

CONSTRUCTION

- tin-plated copper single wire round conductors of diameter 0.4 mm,

- polyethylene (PE) insulation - identification colour code: black, natural,

- insulated conductors twisted into pairs,

- pair shields incorporating aluminium-polyester tape and annealed tinned copper single drain wire,

- shielded pairs laid-up in layers,

- cable core filled petro-gel and wrapped in a polyester tape,

- moisture barrier and additional cable shielding made of a plastic laminated aluminium tape and a drain wire under the tape longitudinally applied over the cable core,

- black polyethylene (PE) cable sheath.

CHARACTERISTICS

Characteristic impedance

120 ± 15 Ω

Mutual capacitance at 1 kHz

60 ± 5 nF/km

Attenuation loss,  max - at frequency 1MHz

4,5 dB/100 m

Near-end cross-talk at 1 MHz, min

60 dB

Insulation resistance, minimum

1000 MΩ·km

Operating voltage

150 V

Voltage test

700 V sk

DC loop resistance at 20°C, max

290 Ω/km

Operating temperature range

during operation

od - 40 do + 70 °C

during installation

od - 10 do + 50 °C

Minimum bending radius

15 x cable diameter

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and pair counts available on request.