CONTROL AND POWER SUPPLY FLEXIBLE CABLES | Technical Data sheet |
|
|
APPLICATIONS
YStY 300/500 V and YStYżo 300/500 V are flexible cables intended for control, protection and monitoring systems or power supply, all in power engineering. The cables are also intended for wiring industrial plants, such as production lines, air-conditioning equipment etc.
The cables are suitable for connecting fixed and movable equipment in dry or wet locations.
Cable outer sheath is oil-resistant.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,
- black PVC insulation and white conductor numbers printed on it for identification,
- insulated conductors laid-up in layers, green-yellow protective conductor located in the outer layer in YStYżo 300/500 V cable,
- PVC cable sheath, grey RAL 7001, other colours also available.
AVAILABLE UPON REQUEST
YStY-O 300/500 V and YStYżo-O 300/500 V - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN-EN 60811-404.
YnStY 300/500 V and YnStYżo 300/500 V - cables of reduced combustibility, sheathed with special self-extinguishing PVC of high oxygen index and pass combustibility test according to PN-EN 60332-3 standard.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.5 |
0.75 |
1.0 |
1.5 |
2.5 |
4.0 |
DC conductor resistance at 20°C, maximum |
Ω/km |
39.0 |
26.0 |
19.5 |
13.3 |
7.98 |
4.95 |
Conductor cross-section |
mm2 |
6.0 |
10 |
16 |
25 |
35 |
50 |
DC conductor resistance at 20°C, maximum |
Ω/km |
3.30 |
1.91 |
1.21 |
0.780 |
0.554 |
0.386 |
Operating voltage Uo/U Voltage test Insulation resistance, minimum Conductor temperature limit in work conditions at short-circuit |
300/500 V 3.0 kV rms 20 MΩ·km
+ 70°C + 150°C |
Operating temperature range for fixed installation for movable installation Minimum bending radius Cable combustibility Combustibility tests Reference standards |
from - 30 to + 80°C from - 5 to + 70°C 7.5 x cable diameter flame retardant PN-EN 60332-1-2, IEC 60332-1-2 WT-91/K-376 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.