CONTROL AND POWER SUPPLY FLEXIBLE CABLES | Technical Data sheet |
|
|
APPLICATIONS
TECHNOKONTROL YnKSLYekw-P 300/500 V and TECHNOKONTROL YnKSLYekw-P-Nr 300/500 V are multipair flexible, overall shielded, flame retardant cables designed for control, protection and monitoring systems or power supply, all in power engineering.
The cable sheath is then made of special self-extinguishing PVC of high oxygen index and pass combustibility test according to PN-EN 60332-3 standard.
Paired structure decreases mutual influence between signals transmitted along the cable.
The cable is protected by an overall electrostatic shield against external electric interferences and prevents emission of interferences produced in the cable.
The cables are designed to offer high flexibility combined with tensile strength.
The cables are suitable for indoor installations connecting fixed and movable equipment.
Cable outer sheath is oil-resistant.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,
- PVC insulation - identification colour code according to PN-92/T-90321 (compatible with IEC 60189-2) in TECHNOKONTROL YnKSLYekw-P 300/500 V cable; black and brown PVC insulation and white pair numbers printed on it for identification in TECHNOKONTROL YnKSLYekw-P-Nr 300/500 V cable,
- insulated conductors twisted into pairs,
- pairs laid-up in layers into a cable core,
- cable core wrapped in polyester tape,
- overall electrostatic shield incorporating aluminium-polyester tape and stranded annealed tinned copper drain wire,
- black (RAL 9005) special self-extinguishing PVC cable sheath, other colours also available.
AVAILABLE UPON REQUEST
TECHNOKONTROL YnKSLYekw-P-O 300/500 V and TECHNOKONTROL YnKSLYekw-P-Nr-O 300/500 V - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN-EN 60811-404.
TECHNOKONTROL YnvKSLYekw-P 300/500 V and TECHNOKONTROL YnvKSLYekw-P-Nr 300/500 V - cables with enhanced PVC sheath, suitable for outdoor installation and direct earth burial.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.5 |
0.75 |
1.0 |
1.5 |
2.5 |
DC loop resistance at 20°C, maximum |
Ω/km |
78.0 |
52.0 |
39.0 |
26.6 |
16.0 |
Operating voltage Uo/U Voltage test Insulation resistance, minimum Conductor temperature limit in work conditions at short-circuit |
300/500 V 3.0 kV rms 20 MΩ·km
+ 70°C + 150°C |
Operating temperature range for fixed installation for movable installation Minimum bending radius Cable combustibility Combustibility tests Reference standards |
from - 30 to + 80°C from - 5 to + 70°C 10 x cable diameter flame retardant PN-EN 60332-1-2, IEC 60332-1-2 PN-EN 60332-3-24, IEC 60332-3-24 (cat. C) WT-TK-17 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and pair counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.