XLPE INSULATED AND PVC SHEATHED, STEEL WIRE ARMOURED AND PVC OVERSHEATHED CONTROL CABLES | Technical Data sheet |
|
|
APPLICATIONS
YKSXSFoyżo-Nr 0,6/1 kV and YKSXSFoy-Nr 0,6/1 kV armoured control cables are designed for control, protection and monitoring systems in power engineering, also for electric power distribution.
The cables are suitable for industrial applications, such as production plants or air-conditioning systems operating in dry and wet locations, also for outdoor installations, in cable ducts or for direct earth burial.
Improved electrical properties, small dimensions and weight compared to the cables with PVC insulation is achieved using cross-linked polyethylene insulation.
Galvanized steel wire armour provides carrying an axial load of the cable during installation and exploitation. It also offers enhanced protection against mechanical damages and rodent attack, as well as shielding properties.
CONSTRUCTION
- bare annealed copper conductors meeting requirements of class 1 per PN-EN 60228 standard,
- black cross-linked polyethylene (XLPE) insulation and white conductor number printed on it; a green-yellow protective conductor in the outer layer in YKSXSFoyżo-Nr 0,6/1 kV cable,
- insulated conductors laid-up in layers,
- PVC cable sheath,
- galvanized steel wire armour,
- black PVC cable covering, other colours also available.
AVAILABLE UPON REQUEST
YKSXSFoyżo-Nr-O 0,6/1 kV and YKSXSFoy-Nr-O 0,6/1 kV - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN-EN 60811-404.
XnKSXSFoxnżo-Nr 0,6/1 kV and XnKSXSFoxn-Nr 0,6/1 kV - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.
CHARACTERISTICS
Conductor cross-section |
mm2 |
1 |
1,5 |
2,5 |
4 |
6 |
10 |
16 |
DC conductor resistance at 20°C, maximum |
Ω/km |
18.1 |
12.1 |
7.41 |
4.61 |
3.08 |
1.83 |
1.15 |
Operating voltage Uo/U 0.6/1 kV
Voltage test 4 kV rms
Insulation resistance, minimum 100 MΩ·km
Conductor temperature limit
in work conditions +90°C
in short-circuit +250°C
Temperature range
during operation from - 30 to + 70°C
during installation from - 5 to + 50°C
Minimum bending radius 12 x cable diameter
Cable combustibility flame retardant
Combustibility tests PN-EN 60332-1-2, IEC 60332-1-2
Reference standards IEC 60502-1, PN-HD 603 S1
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.