XLPE INSULATED AND HALOGEN FREE SHEATHED CONTROL CABLES | Technical Data sheet |
|
|
APPLICATIONS
N2XH-O 0,6/1 kV and N2XH-J 0,6/1 kV power cables are designed for electric power transmission. They are also applied in control, protection and monitoring systems in power engineering.
The cables are suitable for industrial applications, such as production plants or air-conditioning systems operating in dry and wet locations, also for outdoor installations. Cables can be laid in concrete. Laying cables in water or direct earth burial is only permitted if additional protection is used.
Halogen free cables shall be applied in locations where, in case of fire, higher safety for human beings and expensive electronic equipment is required. The cables are flame retardant and their smoke emission is low, emitted fumes are non toxic and non corrosive.
CONSTRUCTION
- bare annealed copper conductors meeting requirements of PN-EN 60228 standard:
RE - class 1 circular single-wire,
RM - class 2 circular multi-wire,
SM - class 2 sector shaped multi-wire.
- cross-linked polyethylene (XLPE) insulation, colours:
in accordance with PN-HD 308 standard,
or black and white conductor number printed on it;
green-yellow protective conductor in the outer layer in N2XH-J 0,6/1 kV cable,
- insulated conductors laid-up into a cable core,
- inner covering made of halogen free compound (HFFR),
- cable sheath made of halogen free compound (HFFR), black, other colours also available.
AVAILABLE UPON REQUEST
Steel wire or steel tape armoured cables as above applied in locations where enhanced protection against mechanical damages is required.
CHARACTERISTICS
Conductor cross-section |
mm2 |
1,5 |
2,5 |
4 |
6 |
10 |
16 |
25 |
35 |
DC conductor resistance at 20°C, maximum |
Ω/km |
12.1 |
7.41 |
4.61 |
3.08 |
1.83 |
1.15 |
0.727 |
0.524 |
Conductor cross-section |
mm2 |
50 |
70 |
95 |
120 |
150 |
185 |
240 |
300 |
DC conductor resistance at 20°C, maximum |
Ω/km |
0.387 |
0.268 |
0.193 |
0.153 |
0.124 |
0.0991 |
0.0754 |
0.0601 |
Operating voltage Uo/U |
0.6/1 kV |
Voltage test |
4 kV rms |
Insulation resistance, minimum |
100 MΩ·km |
Corrosivity of emitted gases per |
PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2 |
pH appr. |
6,8 |
conductivity appr. |
0,4 µS/mm |
Smoke density per |
PN-EN 61034-2, IEC 61034-2 |
minimum light transmittance |
70% |
Conductor temperature limit |
|
in work conditions |
+90°C |
in short-circuit |
+250°C |
Operating temperature range |
|
during operation |
from -30 to +90°C |
during installation |
from -5 to +50°C |
Minimum bending radius: |
|
single core cables |
15 x cable diameter |
multi core cables |
12 x cable diameter |
Cable combustibility |
flame retardant |
Combustibility tests |
PN-EN 60332-1-2, IEC 60332-1-2 |
>= 25 mm2 |
PN-EN 60332-3-23, IEC 60332-3-23 (cat. B) |
< 25 mm2 |
PN-EN 60332-3-24, IEC 60332-3-24 (cat. C) |
Reference standards |
PN-HD 604 S1, IEC 60502-1, DIN VDE 0276 part 604 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.