FIBRE OPTIC SAFETY CABLES | Technical Data sheet |
|
|
APPLICATIONS
TECHNOFLAME FOC-2-SLT-HFFR PH120/E30-E60 50/125 OM2 is fire resistant and water-proof fiber optic cable with one central loose tube (up to 6 fibres) intended for use in fire alarm and fire automatic control systems. Cable can be installed in the buildings, tunnels and underground.
Halogen-free cable, applied when higher safety in case of fire is required. The cable is flame retardant, its smoke emission in fire is low and released gases are not corrosive.
Fibreglass yarns armour provides enhanced protection against mechanical damages and rodent attack. It’s also prevent water from reaching the cable core.
The cables are certified by Scientific and Research Development Centre for Fire Protection (Centrum Naukowo-Badawcze Ochrony Przeciwpożarowej) at Józefów.
The cables are resistant to water in accordance with the standard PN-EN 50200 Annex E. TECHNOFLAME FOC-2-SLT-HFFR PH120/E30-E60 50/125 OM2 cables can be used in fire protected rooms with fixed pressure water spraying fire extinguishing systems (sprinkler zones).
The cables are suitable for indoor and outdoor installations.
CONSTRUCTION
– coloured multi-mode fibres 50/125 OM2,
– loose tube (gel filled) (up to 6 fibres in one tube, colours: red, green, blue, yellow, white, gray), diameter 2,5 ± 0,5 mm,
– double fireproof layer,
– water swelling glass yarns reinforcement,
– reinforcement wrapped in a mica tape,
– red cable outer sheath made of halogen free compound (HFFR) UV stabilized.
CHARACTERISTICS
Attenuation coefficient max
at 850 nm ≤ 2.3 dB/km;
at 1300 nm ≤ 0.5 dB/km;
Core diameter 50 μm
Cladding diameter 125 μm
Coating diameter 250 μm
Operating temperature range
after installation from - 30 to + 70°C
during installation from - 5 to + 50°C
Minimum bending radius
static 10 x cable diameter
dynamic 15 x cable diameter
Maximum pulling tension
after installation 1500 N
during installation 2000 N
Crush resistance
continuous 2000 N
short term 5000 N
Corrosivity of emitted gases per PN-EN 60754-1/-2, IEC 60754-1/-2
pH, >4.3
conductivity, <2.5 µS/mm
Smoke density PN-EN 61034-2, IEC 61034-2
light transmittance, minimum 80%
Cable combustibility fire resistant
Combustibility tests PN-EN 60332-1-2, IEC 60332-1-2
System circuit integrity acc. to PN-EN 50582 *):
do 60 min (E30-E60) DIN 4102-12
P60-R CSN 73 0895
PS 60 STN 92 0205
PH120 PN-EN 50200 + Annex E
Reference standards CNBOP-PIB-KOT-2020/0196-3701 edition 2 and WT-TK-51
Reaction to fire (PN-EN 13501-6): Cca-s1a,d0,a1
*) The maximum change in attenuation of optical fibers according to PN-EN 50582 is 2 dB/m and depends on the cable installation method.
Cable installation – only certified cable fixing systems shall be used. Systems certified according to DIN 4102 part 12 or PN-EN 50200.
Manufacturer |
Circuit integrity |
Cable supporting system |
BAKS |
30 min (E30) |
KSA – cable clips in spacing 600 mm; OZM– cables group hangers in spacing 600 mm, KDS/KDSO60H60 – mash trays 1500 mm |
BAKS |
60 min (E60) |
UDF – cable clips in spacing 300 mm |
OBO BETTERMANN |
30 min (E30) |
1015-8 – cable clips in spacing 300 mm |
Product number |
No of fibres |
Tube diameter [mm] |
Cable outer diameter, (appr.) [mm] |
Cable weight, (appr.) [kg/km] |
2000 001 |
4x50/125 OM2 |
2.5 ± 0.5 |
7.8 |
80 |
Other number of fibres counts available on request.