CONTROL AND POWER SUPPLY FLEXIBLE CABLES Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

HSLH-JZ 0,6/1 kV, HSLH-OZ 0,6/1 kV, HSLH-JB 0,6/1 kV and HSLH‑OB 0,6/1 kV are flexible cables intended for control, protection and monitoring systems or power supply, all in power engineering. The cables are also intended for wiring industrial plants, such as production lines, air-conditioning equipment etc.

Halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.

The cables are designed to offer high flexibility combined with tensile strength.

The cables are suitable for indoor and outdoor installations in dry and wet locations, also for direct earth burial.

Sheathing black halogen free material is resistant to UV radiation.

Cable outer sheath is oil-resistant.

CONSTRUCTION                                                                                                           

- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,

- insulation made of halogen free compound (HFFR), identification colour code:

    HSLH-OZ 0,6/1 kV - black and white conductor number printed on it,

    HSLH‑OB 0,6/1 kV - colours in accordance with PN-HD 308 standard, green-yellow protective conductor located in the outer layer in HSLH-JZ 0,6/1 kV and  HSLH‑JB 0,6/1 kV cable,

- insulated conductors laid-up in layers,

- black cable sheath made of halogen free compound (HFFR).

CHARACTERISTICS

Conductor cross-section

mm2

0.5

0.75

1.0

1.5

2.5

4.0

DC conductor resistance at 20°C, maximum

Ω/km

39.0

26.0

19.5

13.3

7.98

4.95

Conductor cross-section

mm2

6.0

10

16

25

35

50

DC conductor resistance at 20°C, maximum

Ω/km

3.30

1.91

1.21

0.780

0.554

0.386

 

Operating voltage Uo/U

0.6/1 kV

Voltage test

4 kV rms

Insulation resistance, minimum

20 MΩ·km

Conductor temperature limit

in work conditions

+ 70°C

at short-circuit

+ 160°C

Operating temperature range

for fixed installation

from - 40 to + 80°C

for movable installation

from  - 5 to + 70°C

Minimum bending radius

7.5 x cable diameter

Corrosivity of emitted gases per

PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2

pH, appr.

6,8

conductivity appr.

0,4 µS/mm

Smoke density

PN-EN 61034-2, IEC 61034-2

light transmittance, min

70%

Cable combustibility

flame retardant

Combustibility tests

PN-EN 60332-1-2, IEC 60332-1-2

Reference standards

WT-TK-50

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.