HALOGEN FREE HOOK-UP WIRES | Technical Data sheet |
|
|
APPLICATIONS
LiH are hook-up wires intended for control and instrumentation circuits, for signal, monitoring and data processing systems, all for industrial electronic applications.
Halogen free wires, applied when higher safety in case of fire is required. The wires are flame retardant, their smoke emission in fire is low and released gases are not corrosive.
They are designed for control cabinets, electronic devices and others as interconnection cables for electronic modules, equipment and instruments.
CONSTRUCTION
- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,
- insulation made of halogen free compound (HFFR) - coloured according to customer’s requirement.
CHARACTERISTICS
Conductor cross-section |
mm2 |
0.5 |
0.75 |
1.0 |
1.5 |
2.5 |
DC conductor resistance at 20°C, maximum |
Ω/km |
39.0 |
26.0 |
19.5 |
13.3 |
7.98 |
Operating voltage Uo/U |
300/300 V |
Insulation resistance, minimum |
20 MΩ·km |
Voltage test |
1,5 kV sk |
Corrosivity of emitted gases per |
PN-EN 60754-1, PN-EN 60754-2, IEC 60754-2 |
pH appr. |
6,8 |
conductivity appr. |
0,4 µS/mm |
Smoke density |
PN-EN 61034-2, IEC 61034-2 |
minimum light transmittance |
70% |
Operating temperature range |
|
for fixed installation |
from -30 to +70°C |
for movable installation |
from -5 to +70°C |
Minimum bending radius |
7,5 x wire diameter |
Wire combustibility |
flame retardant |
Combustibility tests |
PN-EN 60332-1-2, IEC 60332-1-2 |
Reference standards |
DIN VDE 0815 |
The cable meets requirements of the low voltage directive 2014/35/EU
Other conductor cross-sections available on request.
TECHNOKABEL S.A. reserves the right to change specifications without prior notice.