CONTROL AND POWER SUPPLY FLEXIBLE CABLES Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

TECHNOKONTROL YKSLXS-Nr 300/500 V and TECHNOKONTROL YKSLXSżo-Nr 300/500 V are cables intended for control, protection and monitoring systems, also for power supply, all in power engineering.

Small mutual capacitance and higher, up to 90°C, operating temperature limit of conductors is offered due to application of cross-linked polyethylene insulation.

The cables are suitable for indoor installations connecting fixed and movable equipment.

Cable outer sheath is oil-resistant.

CONSTRUCTION

- flexible, multiwire conductors, stranded of bare annealed copper wires (tin-plated on request), meeting requirements of class 5 per PN-EN 60228,

- black cross-linked polyethylene (XLPE) insulation and white conductor number printed on it,

- insulated conductors laid-up in layers, green-yellow protective conductor located in the outer layer in YKSLXSżo-Nr 300/500 V cable,

- cable core wrapped in polyester tape,

- black (RAL 9005) PVC cable sheath, other colours also available.

AVAILABLE UPON REQUEST

TECHNOKONTROL YKSLXS-Nr-O 300/500 V and TECHNOKONTROL YKSLXSżo-Nr-O 300/500 V - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN-EN 60811-404.

TECHNOKONTROL HKSLXS-Nr 300/500 V and TECHNOKONTROL HKSLXSżo-Nr 300/500 V - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.

TECHNOKONTROL YvKSLXS-Nr 300/500 V and TECHNOKONTROL YvKSLXSżo-Nr 300/500 V - cables with enhanced PVC sheath, suitable for outdoor installation and direct earth burial.

 

CHARACTERISTICS

Conductor cross-section

mm2

0.5

0.75

1.0

1.5

2.5

4.0

DC conductor resistance at 20°C, maximum

Ω/km

39.0

26.0

19.5

13.3

7.98

4.95

Capacitance between conductors at 1 kHz, appr.

nF/km

60

60

60

70

70

80

Conductor cross-section

mm2

6.0

10

16

25

35

50

DC conductor resistance at 20°C, maximum

Ω/km

3.30

1.91

1.21

0.780

0.554

0.386

Capacitance between conductors at 1 kHz, appr.

nF/km

80

80

80

80

80

80

 

Operating voltage Uo/U

Voltage test

Insulation resistance, minimum

Inductance, approximate

Conductor temperature limit

        in work conditions

        at short-circuit

300/500 V

3.0 kV rms

100 MΩ·km

0.7 mH/km

 

+ 90°C

+ 250°C

Operating temperature range

      for fixed installation

      for movable installation

Minimum bending radius

Cable combustibility

Combustibility tests

 

from - 30 to + 80°C

from   - 5 to + 70°C

7.5 x cable diameter

flame retardant

PN-EN 60332-1-2, IEC 60332-1-2

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.

 

.