PVC INSULATED AND SHEATHED, COPPER TAPE SHIELDED AND PVC OVERSHEATHED CONTROL CABLES | Technical Data sheet |
|
|
APPLICATIONS
YKSYektmyżo-Nr 0,6/1 kV and YKSYektmy-Nr 0,6/1 kV shielded control cables are designed for control, protection and monitoring systems in power engineering, also for electric power distribution.
The cables are suitable for industrial applications, such as production plants or air-conditioning systems operating in dry and wet locations, also for outdoor installations, in cable ducts or for direct earth burial.
Copper tape overall shield prevents emission of interferences produced in the cables and protects the cables against external electromagnetic interferences.
CONSTRUCTION
- bare annealed copper conductors meeting requirements of class 1 per PN-EN 60228 standard,
- black PVC insulation and white conductor number printed on it; a green-yellow protective conductor in the outer layer in YKSYektmyżo-Nr 0,6/1 kV cable,
- insulated conductors laid-up in a cable core,
- PVC cable sheath,
- copper tape shield,
- black PVC cable covering, other colours also available.
AVAILABLE UPON REQUEST
YKSYektmyżo-Nr-O 0,6/1 kV and YKSYektmy-Nr-O 0,6/1 kV - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN-EN 60811-404.
XnKSXSektmxnżo-Nr 0,6/1 kV and XnKSXSektmxn-Nr 0,6/1 kV - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.
CHARACTERISTICS
Conductor cross-section |
mm2 |
1 |
1,5 |
2,5 |
4 |
6 |
10 |
16 |
DC conductor resistance at 20°C, maximum |
Ω/km |
18.1 |
12.1 |
7.41 |
4.61 |
3.08 |
1.83 |
1.15 |
Operating voltage Uo/U 0.6/1 kV
Voltage test 4 kV rms
Insulation resistance, minimum 20 MΩ·km
Conductor temperature limit
in work conditions +70°C
in short-circuit +160°C
Temperature range
during operation from - 30 to + 70°C
during installation from - 5 to + 50°C
Minimum bending radius 12 x cable diameter
Cable combustibility flame retardant
Combustibility tests PN-EN 60332-1-2, IEC 60332-1-2
Reference standards IEC 60502-1, PN-93/E-90403, PN-HD 603 S1
The cable meets requirements of the low voltage directive 2014/35/EU
Other cross-sections and conductor counts available on request.