XLPE INSULATED AND PVC SHEATHED, COPPER TAPE SHIELDED AND PVC OVERSHEATHED POWER CABLES Technical Data sheet
 

 

 acrobat reader_50x50  

APPLICATIONS

YKXSektmynżo 0,6/1 kV and YKXSektmyn 0,6/1 kV shielded power cables are designed for electric power transmission. They are also applied in power circuits in industrial plants and power stations and in local distribution networks.

The cables are suitable for indoor and outdoor installations, for laying in cable ducts and for direct earth burial.

Improved electrical properties, small dimensions and weight compared to the cables with PVC insulation is achieved using cross-linked polyethylene insulation.

Copper tape overall shield prevents emission of interferences produced in the cables and protects the cables against external electromagnetic interferences.

The cable sheath is then made of special self-extinguishing PVC of reduced combustibility and pass combustibility test according to EN 60332-3 standard.

CONSTRUCTION                                                                                                          

- bare annealed copper conductors meeting requirements of PN-EN 60228 standard:

              RE - class 1 circular single-wire,

              RM - class 2 circular multi-wire,

              SM - class 2 sector shaped multi-wire.

- cross-linked polyethylene (XLPE) insulation - colours in accordance with PN-HD 308 standard, green-yellow protective conductor in YKXSektmynżo 0,6/1 kV cable,

- insulated conductors laid-up in a cable core,

- PVC cable sheath,

- copper tape shield,

- black PVC cable covering, other colours also available.

AVAILABLE UPON REQUEST

YKXSektmyżo-O 0,6/1 kV and YKXSektmy-O 0,6/1 kV - cables designed for frequent contact with petroleum products, as in petrol stations and stores, where engine fuels and lubricants are pumped or handled. The cable sheath is then made of special PVC compound meeting oil resistance requirements of Polish standard PN‑EN 60811-404.

XnKXSektmxnżo 0,6/1 kV and XnKXSektmxn 0,6/1 kV - halogen free cables, applied when higher safety in case of fire is required. The cables are flame retardant, their smoke emission in fire is low and released gases are not corrosive.

CHARACTERISTICS

Operating voltage Uo/U    0.6/1 kV
Voltage test    4 kV rms
Insulation resistance, minimum    100 MΩ·km

Conductor temperature limit
      in work conditions            +90°C
      in short-circuit                 +250°C

Temperature range
             during operation            from - 30 to + 70°C
             during installation          from   - 5 to + 50°C

Minimum bending radius

      single wire cables           15 x cable diameter

      multi wire cables            12 x cable diameter

Cable combustibility              flame retardant

Combustibility tests                      PN-EN 60332-1-2, IEC 60332-1-2

                   ³ 25 mm2                PN-EN 60332-3-23, IEC 60332-3-23 (cat. B)

                   < 25 mm2               PN-EN 60332-3-24, IEC 60332-3-24 (cat. C)

Reference standards                    IEC 60502-1, PN-HD 603 S1

The cable meets requirements of the low voltage directive 2014/35/EU

Other cross-sections and conductor counts available on request.

TECHNOKABEL S.A. reserves the right to change specifications without prior notice.